Whether expansion anchors or bonded anchors: for distributors and users, it is essential that anchors provide the required corrosion resistance and are suitable and approved for their intended application. But which material is the right choice for which environment?
The key factors are primarily the steel used and its corrosion protection. The applicable requirements depend on the environmental conditions at the installation location and the specifications of the respective European Technical Assessment (ETA).
Normative framework: What role does the ETA play?
Anchors are often technically assessed on the basis of an assumed working life of 50 years. This assumption is based on the concept of the design working life of structures in accordance with the European design standards (Eurocodes) and is specified in the respective European Assessment Documents (EADs).
It is important to note that the assumed working life of 50 years does not constitute a blanket guarantee of service life. It must be understood in the context of the product-specific assessment and the intended conditions of use.
The relevant document for selecting a suitable anchor is the respective European Technical Assessment (ETA). It specifies the conditions of use and also provides information on durability and the required corrosion protection properties.
Depending on the product and its ETA, the corrosion protection requirements can generally be assigned to three application areas:
- Dry indoor conditions: zinc-plated steel, stainless steel or highly corrosion-resistant steel
- Outdoor areas, including industrial atmospheres and locations near the sea, or damp environments where no particularly aggressive conditions are present: stainless steel or highly corrosion-resistant steel
- Outdoor areas and damp environments with particularly aggressive conditions: highly corrosion-resistant steel
Particularly aggressive conditions include, for example, permanent or alternating immersion in seawater, the seawater splash zone, chlorine-containing atmospheres in indoor swimming pools, and environments with heavy chemical pollution. Examples include flue gas desulphurisation plants and road tunnels where de-icing agents are used.
The specific requirements must always be checked against the respective ETA and the actual installation conditions.
Stainless steels and EN 1993: Which corrosion resistance class Is the right one?
There are many different stainless steels, including the aforementioned highly corrosion-resistant stainless steel (High Corrosion Resistance – HCR).
For a more detailed classification, ETAs refer to the Corrosion Resistance Classes (CRC) as defined in EN 1993. More recent ETAs issued on the basis of EAD 330232 (mechanical anchors) or EAD 330499 (chemical anchors) also define the various conditions of use, including environmental conditions, by making direct reference to EN 1993-1-4.
- Components under the conditions of dry indoor environments: all materials
- For other conditions, in accordance with the CRC specified in EN 1993-1-4:2006 + A1:2015: stainless steel in accordance with Annex A3, Table A2 of the respective ETA
Three classes are particularly relevant in anchoring technology:
| Corrosion resistance according to EN 1993-1-4 | Example stainless steel grades |
| CRC II | A2, e.g. material number 1.4301 or 1.4307 |
| CRC III | A4, e.g. material number 1.4401 or 1.4404 |
| CRC V | HCR, e.g. material number 1.4529 or 1.4565 |
The austenitic stainless steels A2 and A4 are the most widely known representatives of their respective material groups. In addition, duplex steels, for example, can also be assigned to the corresponding corrosion resistance classes, depending on the material and its classification under the applicable standards.
The required class depends, among other things, on the Corrosion Resistance Factor (CRF). This is determined in accordance with EN 1993-1-4 on the basis of various environmental parameters. These include, in particular, exposure to salt water and sulphur dioxide, as well as the extent to which rain can wash the surface.
Zinc-coated steels and EN ISO 9223: How does the environment affect service life?
Anchors made of carbon steel with a zinc coating have an important characteristic: depending on the type and thickness of the zinc coating, they may also be suitable for certain applications outside dry indoor environments.
While electroplated anchors often have zinc coatings of approximately 5 micron, hot-dip galvanising and sherardising typically produce significantly thicker coatings. For the products considered here, these are approximately 50 micron and 45 micron, respectively.
Under the conditions specified in the relevant approvals, such anchors can also be used outdoors or in damp environments. However, their possible applications are limited and must be checked against the ETA. For the applications considered here, particular attention must be paid to the requirement for uncracked concrete.
Unlike an application assessed for a 50-year working life using suitable stainless steel, the achievable working life of zinc-coated anchors can be significantly reduced depending on the corrosivity (C) of the environment.
The corrosivity categories are defined in EN ISO 9223. They range from C1 (very low corrosivity) to C5 (very high corrosivity), as well as CX (extreme corrosivity).
For the hot-dip galvanised MKT products B bolt anchors (ETA-01/0013) and V-A anchor rods used in combination with VMH injection mortar (ETA-17/0715), the following working lives apply depending on the corrosivity category, in accordance with the respective approval conditions:
| Corrosivity according EN ISO 9223 | Working life by years | ||
| Category | B fvz | V-A fvz / VMH | |
| C1 | Very low | 50 | 50 |
| C2 | Low | 50 | 50 |
| C3 | Medium | 25 | 25 |
| C4 | High | 12,5 | 12,5 |
| C5 | Very high | 5,5 | 5 |
| CX | Extremely high | 2 | 2 |
The use of hot-dip galvanised anchors can therefore be an economical alternative to stainless steels. The requirement is that the intended working life, the environmental conditions and the product-specific approval conditions are compatible.
Safety starts with choosing the right material for the environmental conditions
The apparent cost advantage of choosing a less expensive material can quickly turn into the opposite. If the corrosion protection is inadequate, corrosion may begin earlier than expected. Possible consequences include a reduction in the cross-sectional area, a decrease in load-bearing capacity and, in extreme cases, failure of the fastening. This is particularly critical in structural applications, where failure can endanger people or cause considerable property damage.
The problem is that an unsuitable material choice often only becomes apparent after several years, for example through visible rust spots or loosening anchors. The necessary remedial work can be extensive: anchors must be removed, drill holes repaired and new anchors installed. This incurs additional costs and can compromise the operational safety of an installation.
Responsibility for proper installation is another important aspect. If anchors are used contrary to applicable requirements or the specifications of their ETA, this can give rise to significant liability risks. Choosing the correct corrosion resistance class is therefore not only a matter of cost-effectiveness but also an essential part of safe and standards-compliant fastening.
The selection of the anchor material has a decisive influence on the durability and safety of an anchoring. The ETA provides information on which materials may be used under the respective environmental conditions. Zinc-plated anchors may be sufficient for permanently dry indoor environments. In outdoor areas and damp environments, stainless steels are generally required. Whether A2 or A4 is sufficient depends on the specific exposure and the requirements of the ETA. Under particularly aggressive conditions, such as chlorine-containing atmospheres in indoor swimming pools, highly corrosion-resistant steel (HCR) may be required. Hot-dip galvanised anchors can also provide an economical solution under the approved conditions. However, their permissible working life depends on the corrosivity of the environment and may be significantly less than 50 years.